Technical specification

Capacity
80 – 2320 Ah

nominal voltage
2 V DC

expected operating life
15 years

SD - SDH RANGE IS THE PERFECT CHOICE WHEN APPLICATION REQUIRES HIGH POWER IN A SHORT PERIOD OF TIME.

The range is constructed to provide a high level of robustness and designed for applications where high energy peaks are needed in a short timeframe. Due to a special low antimony plates design the range offers users the benefit of low maintenance result in improved operating costs.

Batteries need topping-up once every three years under normal operating conditions. Furthermore the design is optimized to offer very low self-discharge for long storage period without a refreshing charge. Like all Fiamm lead-acid batteries the SD - SDH range is eco-friendly and fully recyclable.


GENERAL FEATURES

Specifications

  • The flat plates design provides a larger active surface area; the result is maximum performance with a high rate discharge.
  • Electrolyte: sulphuric acid electrolyte with specific gravity of 1.27 kg/l at 20°C.
  • Low internal resistance due to high porosity separators.
  • Robust box construction made of SAN with a flame retardant ABS lid.
  • Flameproof vent plugs made of porous materials for superior safety.
  • A long shelf life of up to six months is possible without recharge (<2% discharge per month)
  • Flat post is designed for high contact area with rigid connection.
  • Rigid copper connections to allow higher currents.

Technology
The unique Fiamm terminal design permits pillar growth during cell life without leakage. The SD-SDH range has a design life is 15 years due to high reliability and components manufacture due to process. Low self-discharge allows up to 6 months without recharge in open circuit condition. All SD-SDH models are available in a dry charge version.

Accessories

  • Recombination plug
  • Filtering plugs to DIN standard
  • Racks for battery installation (standard and anti-seismic)
  • Battery monitoring system

Standards

  • IEC 60896 Part 11 – vented types requirements & tests
  • BS 6290 part 2 - British Standard specification

Certifications

  • ISO 9001 - Quality Management System
  • ISO 14001- Environmental Management System
  • OHSAS 18001 - Workplace Safety & Health

 Electrical Characteristics

  • Float Voltage: 2.23 V/cell at 20°C
  • Boost Voltage: 2.40 V/cell
  • Float Voltage Compensation with Temperature: -2.5 mV/cell/°C
  • Self-Discharge at 20°C: <2%/month

 Application

  • Industrial UPS
  • Industry
  • Oil and gas